Design Idea:
Solar Panel Power Converter
Overcomes Start-Up Problems

Goran Perica

Introduction

Solar panels are difficult to use as power sources for DC/DC converters due to their output characteristics. Figure 1 shows a typical output characteristic for a Siemens SM6 solar panel. Solar panels have almost constant output current in their operating region (0V to 15V for the SM6). They also have high output impedance in the operating region below the peak power point, VPMAX (the SM6 has 10W to 500W output impedance for output voltages VSP < VPMAX). Unfortunately, the output impedance is highest during DC/DC converter start-up, when VSP is below the peak output power point, VPMAX, as shown in Figure 2.


output characteristic of Siemens SM6 solar panel

Figure 1. Output characteristic of Siemens SM6 solar panel at 1000W/m2 and 25°C

Power output of Siemens SM6 solar panel

Figure 1. Power output of Siemens SM6 solar panel at 1000W/m2 and 25°C

A typical power source (a generator or a battery) will deliver more power as the current drain increases. This is true in the region where the load impedance is greater than the output impedance of the power source. For the SM6, this happens in the region where VSP is above VPMAX. In the region below VPMAX, the power output starts decreasing as the current drain increases. In other words, the panel is behaving as a current source for output voltages below VPMAX and as a voltage source for output voltages above VPMAX.

When a DC/DC converter is connected to a solar panel, the start-up inrush current caused by the converter's negative impedance may exceed the peak current rating of the panel, causing the panel output voltage to collapse; this results in a permanent latch-up.

Solar Panel Converter

The circuit shown in Figure 3 overcomes this problem by controlling the inrush current. Normally, a converter has a preset current limit; at start-up, input current surges to its peak value while the converter is trying to bring the output into regulation. Start-up can be even more difficult because the output load may demand full power from the source while the solar panel is still operating in the region below its VPMAX point. Also, the load may have a substantial amount of output filter capacitance that has to be charged, thus requiring additional current from the input.

solar converter schematic

Figure 3. Solar panel DC/DC converter

Vendors of non-LTC components used in this application



Start-up is not a problem if input source can deliver the additional power required to charge the output capacitors, as shown in Figure 4. The waveforms in Figure 4 show the start-up of the circuit in Figure 3, without the components that control the start-up current surge (capacitor CSS removed). As can be seen, the input current surges to the 2A current limit of U1, an LT1308 micropower DC/DC converter, until the output reaches the 5V regulation point (Trace 4). In this case, the peak input current is limited by the current limit of U1.

Inrush current w/o current limit

Figure 4. Inrush current (trace 3, 1A/DIV) with low impedance,
non-current limited power source

If the input power source is current limited, as is the case with a solar panel, the DC/DC converter may latch up in an undervoltage condition, as shown in Figure 5. As soon as U1 starts running, the input current reaches the peak set by the current-limited input power source. In the case of Figure 5, the input power source current limit is set to 0.8A and the converter still won't start. Also, there is an overcurrent transient (time from 32ms to 36ms) caused by the energy stored in the output capacitor of the source power supply.

inrush current with current limited

Figure 5. Inrush current (trace 3, 1A/DIV) with power source
imited to 0.8A

Under this condition, the input voltage (Trace 2) starts to collapse as soon as the load current reaches the preset current limit of 0.8A. Once the source supply's bypass capacitor is discharged and the input voltage collapses to 1.3V, the converter is latched up and can't recover. The output voltage under this condition settles to a value that depends on the load (3V in this case). If an undervoltage lockout were used, the circuit would enter a hiccup mode, trying to restart.

One way of solving this problem is to set the switch current to a lower value and to use a larger solar panel.

Soft-Start Circuit

The circuit in Figure 3 overcomes the start-up inrush current problem by reducing the current limit during start-up. As soon as the output voltage reaches the VBE voltage of Q2, Q2 starts conducting and pulls down on U1's VC pin. The current limit is now reduced to zero. As CSS is being charged, Q2's collector current decreases and the current limit of U1 increases slightly, causing the output voltage to rise. This process will continue until the output voltage reaches regulation and CSS is fully charged. At that point, resistor R4 pulls the base of Q2 to ground, removing Q2 from the circuit. The rise time of the output voltage is dependent on CSS, Q2 and R4. Because the base current of Q2 is very small with respect to the current through resistor R4, the base current of Q4 can be neglected. The value of CSS required to raise the output from zero to the nominal output voltage, VOUT, will be:

equation

where VBE is the base-emitter threshold of Q4 and tON is the desired turn-on time.

Start-up waveforms for the values in Figure 3's circuit are shown in Figure 6. The input current exhibits only a slight surge, reaching only169mA before settling to a steady-state value of 163mA .

The amount of output current that the LT1308 can generate also depends on the input voltage. The relationship between output current and input voltage is shown in Figure 7.



inrush current w current limited

Figure 6. Inrush current (trace 3, 1A/DIV) with power source limited to 0.35A and soft-start circuit

dependence of current on output voltage

Figure 7. Dependence of ouput current on LT1308's input volltage

Conclusion

Inrush current control is a very desirable feature for converters that use a solar panel as a power source. By preventing current transients during start-up, the size of the solar panel can be kept to the minimum required by the steady-state load. The circuit described here can be used with any current mode control IC that has an accessible, high impedance error amplifier output. In this fashion, a converter for solar cell applications of any power level can be built.   LT Logo


Return to the Linear Zone